299 NEC-based practice questions covering branch circuits, conductor sizing, grounding, motor calculations, service entrance, and code compliance. Ace your journeyman or master electrician exam on the first try.
Try your first 25 questions free. Continue with a paid plan.
Load calculations, wire sizing, circuit design, and demand factors
NEC Table 310.16, derating, temperature correction, and conduit fill
Equipment grounding conductors, grounding electrode systems, and bonding
Motor FLC, overload protection, branch circuit sizing, and disconnects
Residential and commercial service load calculations per NEC Article 220
EMT, RMC, PVC, conduit fill calculations, and support requirements
Fuses, circuit breakers, coordination, and selective trip settings
Single-phase and three-phase transformer connections, sizing, and protection
Class I/II/III divisions and zones, equipment selection, and wiring methods
Navigating the NEC, article structure, definitions, and general requirements
Per NEC Table 250.122, a 60-ampere overcurrent protective device requires a minimum 10 AWG copper equipment grounding conductor. This table is based on the rating of the overcurrent device, not the conductor ampacity, ensuring the grounding path can safely carry fault current.
Per NEC 430.52 and Table 430.52, the maximum rating for an inverse-time circuit breaker protecting a squirrel cage motor is 250% of the motor FLC. Using FLC from NEC Table 430.250 (not nameplate): 28A x 2.50 = 70A. Since 70A is a standard breaker size, you would use a 70-amp breaker. Always use the NEC table values for FLC, not the motor nameplate.
Per NEC Chapter 9 Table C.1, a 3/4-inch EMT can accommodate up to 16 conductors of 12 AWG THHN. This is based on the 40% fill rule for three or more conductors. The total area of 16 THHN 12 AWG conductors (each 0.0133 sq in) equals 0.2128 sq in, which is within the 0.213 sq in allowed at 40% fill of the 3/4-inch EMT internal area.
NEC 210.52(A) requires that no point along the floor line of any wall space be more than 6 feet from a receptacle outlet. This means receptacles must be spaced no more than 12 feet apart (6 feet on either side), ensuring that a standard 6-foot appliance cord can reach an outlet from any point along the wall.
Per NEC Table 220.12, dwelling units require a general lighting load of 3 volt-amperes per square foot. For 2,400 sq ft: 2,400 x 3 VA = 7,200 VA. This value is used in service and feeder load calculations and includes all general-use receptacles and lighting outlets. It does not include small appliance or laundry circuits, which are calculated separately.
Per NEC 110.26(A)(1) and Table 110.26(A)(1), the minimum clear working space for Condition 1 (exposed live parts on one side with no live or grounded parts on the other) at 301 to 600 volts is 3 feet (36 inches). The working space must also be at least 30 inches wide or the width of the equipment, whichever is greater, and extend from the floor to a height of 6.5 feet or the height of the equipment.
NEC 210.11(C)(1) requires a minimum of two 20-ampere small-appliance branch circuits to serve all receptacle outlets in the kitchen, pantry, breakfast room, dining room, and similar areas. Each circuit is calculated at 1,500 VA for load calculation purposes, adding 3,000 VA to the service calculation.
Per NEC 210.8(A)(2), all 125-volt, 15- and 20-ampere receptacles installed in garages and accessory buildings with a floor at or below grade require GFCI protection. This applies to all receptacles in the space, not just those near water sources. The only exception is for receptacles that are not readily accessible, such as a ceiling-mounted receptacle for a garage door opener.
Per NEC Table 310.16, a 6 AWG THHN (rated 90°C) copper conductor has an ampacity of 75 amps at 30°C ambient temperature. THHN is rated in the 90°C column of Table 310.16. However, when used with 60°C-rated equipment terminations (common for most equipment under 100A), the conductor must be used at the 60°C column ampacity of 55A per NEC 110.14(C).
The primary full-load current is 10,000 VA / 480V = 20.83A. Per NEC 450.3(B), transformers 600 volts and below with primary overcurrent protection only (no secondary protection) can be protected at a maximum of 125% of primary FLC: 20.83A x 1.25 = 26.04A. Since this does not correspond to a standard fuse or breaker size, NEC 240.6(A) permits rounding up to the next standard size, which is 30 amps.
Access all 299 electrician practice questions with detailed explanations.
Start ExamWe offer 299 electrician practice questions based on the National Electrical Code, covering topics needed for both journeyman and master electrician licensing exams.
Your first 25 questions are free. Continue beyond 25 questions with a paid plan.
The test covers branch circuit calculations, conductor sizing and ampacity, grounding and bonding, motor circuits, service calculations, raceway systems, overcurrent protection, transformers, hazardous locations, and general NEC code application.
Most journeyman and master electrician exams are open-book, allowing you to bring the NEC codebook. Practice navigating the code quickly using our questions that reference specific articles and tables. Familiarity with the code structure is essential for finishing within the time limit.
Register for your Journeyman Electrician exam through Prometric, or check out Ugly's Electrical References.